HXGN17-12 Box-Type AC Metal-Enclosed Ring Main Unit

12kV · 630A · FN/FZ Load Switch Options

The HXGN17-12 box-type metal-enclosed ring main unit is designed for 12kV three-phase AC ring network and terminal distribution, also suitable for integration into box-type substations with FN12-10 or FZN25-12 switch options.


HXGN17-12 — HXGN17-12 Box-Type AC Metal-Enclosed Ring Main Unit12kV

Ring Network & Terminal Use

Box-Type Substation Ready

Factory Direct

Key Specifications

  • Model — HXGN17-12
  • Rated Voltage — 12 kV
  • Rated Current — 630 A
  • Transfer Current — 1500-2000 A
  • Protection — IP2X
  • Standards — GB3906; IEC 60298
  • OEM / ODM — Custom branding and packaging available
Category:

Overview

The HXGN17-12 box-type AC metal-enclosed switchgear (ring network cabinet) produced by RUY Power has a rated voltage of 12KV and a rated frequency of 50HZ AC high-voltage complete set of electrical equipment. It is mainly used for three-phase AC ring network, terminal power distribution network and industrial power equipment, for receiving, distributing electric energy, etc., and is also suitable for being packed into box-type substations.

Normal Operating Environment

1. Ambient air temperature: -15℃ ~ +40℃;

2. Altitude: 1000m and below;

3. Humidity: daily average not greater than 95%, water vapor pressure daily average value not exceeding 2.2kPa; monthly average not greater than 90%, water vapor pressure monthly average value not exceeding 1.8kPa;

4. Earthquake intensity: not exceeding 8 degrees;

5. Places without fire, explosion hazards, chemically corrosive gases and violent vibration.

Note: If the above normal operating conditions are exceeded, users can negotiate with RUY Power.

Main Technical Parameters

No. Name Unit FN12-10 FZN25-12
1 Rated voltage kV 12
2 1min power frequency withstand voltage kV to earth and between phases 42; across isolating fracture 48
3 Lightning impulse voltage (peak value) kV to earth and between phases 75; across isolating fracture 85
4 Rated frequency Hz 50
5 Main busbar rated current A 630
6 Rated current A 630
7 Rated no-load transfer current (load switch) kVA not less than 100
8 Open-circuit transformer capacity kA/s 1250
9 Rated thermal stable current KA 20/4; earth switch 20/2
10 Rated dynamic stable current (peak value) KA 50
11 Rated short-circuit making current (peak value) times 50
12 Fuse rated current A 100
13 Rated transfer current A 1500 2000
14 Combined electrical appliance rated short-circuit breaking current kA 31.5
15 Mechanical life times 2000 10000
16 Secondary loop 1min power frequency withstand voltage kV 2
17 Electric operating mechanism working voltage V AC/DC 220; 110
18 Protection grade IP2X
19 Overall dimension (width × depth × height) mm 650(850)X900X2000(2200)

Overall Dimensions and Foundation Construction

Overall dimension: width 650(850)mm, depth 900mm, height 2200mm; double cabinet width 900mm.

Embedded foundation: embedded parts depth 1000~1200mm, foundation groove width 750mm, reserved hole size 200/300mm, cable trench height 850mm.

Frequently Asked Questions

What is the rated voltage of the HXGN17-12?

The HXGN17-12 Box-Type AC Metal-Enclosed Ring Main Unit operates at 12 kV, suitable for the intended distribution application.

Does the HXGN17-12 support OEM / ODM orders?

Yes. RUY Power provides custom branding, packaging and configuration for the HXGN17-12 Box-Type AC Metal-Enclosed Ring Main Unit to meet project requirements.

What standards does the HXGN17-12 comply with?

The HXGN17-12 Box-Type AC Metal-Enclosed Ring Main Unit is designed and type-tested in accordance with GB3906 and IEC 60298.

What is the lead time for the HXGN17-12?

Standard lead time is 15-30 days depending on configuration and order quantity. Contact RUY Power for a precise delivery schedule.