GN□-12 Solid Insulated Switchgear

12kV · 630-1250A · Eco Solid Epoxy Insulation

The GN□-12 solid insulated switchgear is a new-generation eco-friendly ring main unit with all primary circuits fully embedded in epoxy resin — SF6-free, maintenance-free, with integrated interlocking and 10000-operation mechanical life.


GN□-12 — GN-12 Solid Insulated Switchgear12kV

SF6-Free Solid Insulation

Eco-Friendly Composite

Factory Direct

Key Specifications

  • Model — GN□-12
  • Rated Voltage — 12 kV
  • Rated Current — 630/1250 A
  • Breaking Current — 25/31.5 kA
  • Protection — IP4X
  • Operation — Spring Stored Energy
  • OEM / ODM — Custom branding and packaging available
Category:

Overview

The GN□-12 solid insulated switchgear produced by RUY Power is a new generation of environmentally friendly composite insulated ring network cabinet. It is mainly composed of three types of components, namely V unit (circuit breaker unit), C unit (load switch unit), and T unit (combined electrical unit). Each unit can be used independently or can be self-expanded. The structure is divided into intelligent control and instrument, operating mechanism and secondary part. The instrument chamber is equipped with microcomputer protection (relay control), and one part adopts APG automatic gel technology, which completely seals the isolating switch and the busbar chamber in epoxy resin. Special bushings and wires are insulated. The fire extinguishing special aluminum alloy hardware, RB shape magnetic field, in order to completely complete secondary plugging, opening and closing circuit circuits circuit breaking capacity and stability, motor spring operation, and the operating mechanism, isolating switch and the main switch operating mechanism are integrated, which can conveniently realize interlocking, and mechanism parts are reduced, unnecessary transmission links are reduced, which can be prepared to improve the reliability of the product.

Solid insulated sealed switchgear refers to a module or several modules with a certain function and may be combined or expanded, in which all main circuits and circuits such as main conductive circuits, isolating switches, earthing switches, main busbars, branch busbars, etc. are wrapped or packaged by solid insulating medium.

Switchgear Technical Parameters

Item Unit Value
Rated voltage kV 12
Rated frequency Hz 50
Rated current A 630 / 1250
Rated insulation level power frequency withstand voltage (fracture) kV 48
(phase-to-phase) kV 42
lightning impulse withstand voltage (phase-to-phase) kV 75
(phase-to-earth) kV 75
Rated short-circuit breaking current (1s) kA 25 / 31.5
Rated short-time withstand current (4s) kA 25 / 31.5
Rated peak withstand current (2P) kA 63 / 80
Rated cable charging breaking current (peak value) (1ma) kA 63 / 80
External protection grade IP4X
Operation mode Spring energy storage type

Circuit Breaker Technical Parameters

No. Item Unit Parameter
1 Rated voltage kV 12
2 Rated frequency Hz 50
3 1min power frequency withstand voltage kV 42
Lightning impulse withstand voltage kV 75
4 Rated current A 630 / 1250
5 Rated short-circuit breaking current kA 20 25 / 31.5
6 Rated short-circuit making current (peak value) kA 50 63 / 80
7 Rated peak withstand current kA 50 63 / 80
8 Short-time withstand current (effective value) kA 20 25 / 31.5
9 Rated short-circuit breaking times times 30 / 30
10 Rated short-circuit breaking duration s 4
11 Automatic reclosing operation sequence divide – 0.3s – close – 180s – close (rated short-circuit breaking current is below 31.5kA)
Non-automatic reclosing divide – 180s – close – 180s – close (rated short-circuit breaking current 40kA and below)
12 Mechanical life times 10000

Isolating/Earth Switch Technical Parameters

No. Item Unit Parameter
1 Rated voltage kV 12
2 Rated current A 630 / 1250
3 4s rated short-time withstand current (effective value) kA 25 / 31.5
4 Rated peak withstand current (peak value) kA 63 / 80
5 1min power frequency withstand voltage (between phases and to earth) kV 42
(across isolating fracture) kV 48
Lightning impulse withstand voltage (across isolating fracture) kV 85
6 Main switch mechanical life times 3000
7 Earth switch mechanical life times 3000

Circuit Breaker

No. Item Unit Parameter
1 Arc extinguishing type Vacuum
2 Rated current A 630,1250
3 Rated short-circuit breaking current (AC component effective value) kV 25
4 Operating sequence times 30
5 Rated operation sequence O-0.3s-CO-180s-CO
6 Rated short-time withstand current / duration kA/s 25/4
7 Rated peak withstand current kA 63
8 Rated making current kA 63
9 Average opening/closing speed m/s 1.1±0.2
Closing speed 0.8±0.2
10 Three-phase synchronism ms ≤ 2
11 Contact bounce value at closing mm ≤ 2
12 Opening time ms 30~70
13 Opening time ms 20~50
14 Three-phase opening time difference ms ≤ 2
15 Opposite earth fault breaking test test current kA 21.7
Test voltage kV 12
16 Capacitive current breaking test test current A 25
Test voltage kV 12
17 Main circuit resistance μΩ ≤ 120
18 Mechanical life times 10000

Frequently Asked Questions

What is the rated voltage of the GN□-12?

The GN□-12 Solid Insulated Switchgear operates at 12 kV, suitable for the intended distribution application.

Does the GN□-12 support OEM / ODM orders?

Yes. RUY Power provides custom branding, packaging and configuration for the GN□-12 Solid Insulated Switchgear to meet project requirements.

What standards does the GN□-12 comply with?

The GN□-12 Solid Insulated Switchgear is designed and type-tested in accordance with applicable IEC and GB standards.

What is the lead time for the GN□-12?

Standard lead time is 15-30 days depending on configuration and order quantity. Contact RUY Power for a precise delivery schedule.

Reviews

There are no reviews yet.

Be the first to review “GN□-12 Solid Insulated Switchgear”

Your email address will not be published. Required fields are marked *