Overview
The SRM-12 fully insulated fully sealed metal-enclosed switchgear produced by RUY Power is an SF6 gas insulated metal-enclosed ring main unit. The equipment can be composed of load switch unit, load switch-fuse combined electrical unit, vacuum circuit breaker unit, and busbar incoming unit modules, adopting a series of standard technologies and materials, with excellent electrical performance and mechanical performance, unaffected by the environment (small size), easy to install and operate, maintenance-free, and flexible combination modes. The intuitive equipment design ensures simple and direct operation, large cable connection capacity, suitable for multiple wiring systems.
Unit Definition
| Unit Code | Meaning |
|---|---|
| C | Standard load switch unit |
| F | Load switch-fuse combined unit |
| V | Circuit breaker unit |
| D | Cable incoming unit (without switch) |
| + | Busbar riser |
| – | Busbar bushing |
| SL | Busbar connection unit |
| M | Metering unit |
| PT | PT unit |
| 1K2(4) | Double bushing outgoing load switch unit |
Performance Indicators
SF6 gas pressure: 1.4bar absolute pressure at 20℃
Annual gas leakage rate: 0.2%/year
Protection grade: IP67
Minimum working temperature: -40℃
Main busbar: 400mm²Cu
Cabinet internal earth wire: 150mm²Cu
Color: RAL7012 for switch front panel; RAL7035 for cabinet and cable chamber front panel
Normal operating environmental conditions: maximum temperature 40℃, minimum temperature -40℃, daily average relative humidity ≤ 95%, altitude ≤ 2000m
Standards: GB/T11022, GB3906, GB1985, GB16926, GB39041, GB1984, GB3309, IEC60056, IEC60129, IEC60265, IEC60298, IEC60420, IEC60694
Product Features
Operational safety: through the following safety measures, we can provide users with special safety guarantees:
Integrated three-position load switch
The disconnector adopts a load switch or isolating switch, which is safer and more reliable. The sealed design provides external contact protection to meet the five-prevention requirements of the mechanical interlock with live display, and the incoming/outgoing cable with live display operation reliability: fully sealed design, all 10kV switches and busbars are hermetically sealed in a 3mm thick stainless steel welded gas box; silicon rubber cable connectors realize cable head fully sealed insulation, thereby preventing dust, moisture, small animals and other external environmental effects on the operating mechanism. Manual/electric operation can be manually or electrically operated according to the wiring diagram.
The indicator system is made of impact-resistant material, with electrostatic spraying, which has corrosion resistance. The pressure gauge visually displays the SF6 gas safety pressure range inside the SF6 box.
Economical
Maintenance-free
High reliability
Service life up to 20 years
Flexible schemes
Multiple incoming line modes, which can realize left, right, upper and front incoming lines
Multiple combination modes, which can realize cable connection combination between units
Insulated busbar, which can realize back-to-back left and right parallel connection
Compact design
Widely used
Small outgoing line capacity, small floor space, suitable for various application needs.
Main Technical Parameters
| Item | Unit | C Module Load Switch | F Module Combined Electrical | V Module Vacuum Switch | V Module Isolating/Earth Switch | CB Module Vacuum Circuit Breaker | CB Module Isolating/Earth Switch |
|---|---|---|---|---|---|---|---|
| Rated voltage | kV | 12 | 12 | 12 | 12 | 12 | 12 |
| Rated frequency | Hz | 50 | 50 | 50 | 50 | 50 | 50 |
| Power frequency withstand voltage (phase/fracture) | kV | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 | 42/48 |
| Lightning impulse withstand voltage | kV | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 | 75/85 |
| Rated current | A | 630 | Note | 630 | 1250/630 | ||
| Rated loop breaking current | A | 630 | |||||
| Rated cable charging breaking current | A | 135/135 | |||||
| Rated short-circuit making current (peak value) | 50 | 80 | |||||
| Rated peak withstand current | 50 | ||||||
| Rated short-time withstand current | kA/3s | 20 | |||||
| Rated transfer breaking current | kA | 31.5 | 20 | 25 | 25 | ||
| Rated transfer current | A | 1750 | |||||
| Starting current of fuse maximum current | A | – | 125 | ||||
| Loop resistance | Ω | ≤ 300 | ≤ 600 | ||||
| Mechanical life | times | 5000 | 3000 | 5000 | 2000 | 5000 | 5000 |
Design Description
The SRM-12 fully insulated fully sealed metal-enclosed switchgear is installed on a galvanized sheet frame. The switch unit is in an SF6 gas box. The gas box is made of corrosion-resistant and amagnetic 3mm thick stainless steel plate. The SF6 gas box is a “pressure relief system” which can operate for 20 years under normal working conditions. The normal working pressure of SF6 gas is 0.015~0.04MPa. The gas box has a pressure relief device. When the pressure is too high, the gas box can be released from the bottom or top.
Frequently Asked Questions
What is the rated voltage of the SRM-12?
The SRM-12 Fully Insulated Fully Sealed Metal-Enclosed Switchgear operates at 12 kV, suitable for the intended distribution application.
Does the SRM-12 support OEM / ODM orders?
Yes. RUY Power provides custom branding, packaging and configuration for the SRM-12 Fully Insulated Fully Sealed Metal-Enclosed Switchgear to meet project requirements.
What standards does the SRM-12 comply with?
The SRM-12 Fully Insulated Fully Sealed Metal-Enclosed Switchgear is designed and type-tested in accordance with IEC 60298 and IEC 60420.
What is the lead time for the SRM-12?
Standard lead time is 15-30 days depending on configuration and order quantity. Contact RUY Power for a precise delivery schedule.





Reviews
There are no reviews yet.